When apcupsd detects that the mains are on, but the battery is not functioning correctly, this event is
generated. It is repeated every x hours.
Default: wall a message
commfailure
This event is generated each time the communications line with the computer is severed. This event
is not detected on dumb signaling UPSes.
Default: wall a message
commok
After a commfailure event is issued, when the communications to the computer is re-established, this
event will be generated.
Default: wall a message
doreboot
This event is depreciated and should not be used.
Default: Shuts down the system using shutdown -h or similar
doshutdown
When the UPS is running on batteries and one of the limits expires (time, run, load), this event is
generated to cause the machine to shutdown.
Default: Shuts down the system using shutdown -h or similar
emergency
Called for an emergency system shutdown. (What triggers such a shutdown is unclear...) After
completing this event, apcupsd will immediately initiate a doshutdown event.
Default: wall a message
failing
This event is generated when the UPS is running on batteries and the battery power is exhausted.
The event following this one will be a shutdown.
Default: wall a message
loadlimit
This event is generated when the battery charge is below the low limit specified in the apcupsd.conf
file. After completing this event, apcupsd will immediately initiate a doshutdown event.
Default: wall a message
powerout
This event is generated immediately when apcupsd detects that the UPS has switched to batteries. It
may be due to a short powerfailure, an automatic selftest of the UPS, or a longer powerfailure.
Default: wall a message
onbattery
This event is generated 5 or 6 seconds after an initial powerfailure is detected. It means that apcupsd
definitely considers the UPS to be on batteries. The onset of this event can be delayed by the
ONBATTERYDELAY apcupsd.conf configuration directive.
Default: wall a message
offbattery
This event is generated when the mains return only if the onbattery event has been generated.
Default: wall a message
mainsback
This event is generated when the mains power returns after a powerout condition. The shutdown
event may or may not have been generated depending on the parameters you have defined and the
length of the power outage.
Default: nothing