APC SU1400XLT User Manual Page 63

  • Download
  • Add to my manuals
  • Print
  • Page
    / 115
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 62
The Network Management Card (AP9617, AP9618, AP9619) must be
configured with network settings before it can communicate on the
network. Once the cards have been configured with an IP address,
Subnet Mask, and Default Gateway the cards can be access, managed,
and controlled from other computers on the network.
There are two ways to configure the Network Management Card (NMC)
with its initial settings: the (windows) Wizard and Address
Resolution Protocol (ARP).
1. The wizard in included on the CD that comes with the card. The
wizard must run on a Windows operating system. You can configure
the card using the wizard over the network via FTP. If using the
wizard please note, the un-configured NMC must be on the same
subnet as the computer running the wizard.
2. Address resolution protocol (arp) can also be used to configure
the NMC. The MAC Address of the NMC is needed for this method of
configuration. The MAC address is located on the quality assurance
slip that is shipped with the NMC, and is also located on the white
sticker on the NMC itself. From a computer on the same subnet as
the un-configured NMC, follow the instructions:
Open up a command prompt and type the following (replacing
<IPaddress> and <MacAddress> with the actual values):
arp -s <IPaddress> <MacAddress>
Next, use Ping with a size of 113 bytes to assign the IP address
defined by the ARP command.
- Linux command format: ping <IPaddress> -s 113
- Windows command format: ping <IPaddress> -l 113
Set SNMP card General Parameters
After the SNMP Network Management Card is configured with an IP address, the SNMP Card is ready for
general configuration. This is accomplished by telneting to the SNMP Card.
~$ telnet <IPaddress>
Login using "apc" for both the username and password and the following menu will display:
*******************************************************************************
American Power Conversion Network Management Card AOS v2.6.4
(c) Copyright 2004 All Rights Reserved Smart-UPS & Matrix-UPS APP v2.6.1
-------------------------------------------------------------------------------
Name : Date : 07/03/2006
Contact : Time : 04:43:33
Location : User : Administrator
Up Time : 0 Days 01 Hours 57 Minutes Stat : P+ N+ A+
Smart-UPS 1000 named : On Line, No Alarms Present