following diagram is correct.
This diagram is for informational purposes and may not be complete. We don't recommend that use it to
build you build one yourself.
APC Part# - 940-0023A
Signal Computer UPS
DB9F DB9M
DCD 1 -------------------- 2 On Battery
3.3K ohm
TxD 3 --[####]-*
|
DTR 4 ---------*
GND 5 ---------------*---- 4 Ground
|
*---- 9 Common
940-0024C Cable Wiring
Supported
Models:
SmartUPS (all models with DB9 serial port)
If you wish to build the standard cable furnished by APC (940-0024C), use the following diagram.
APC Part# - 940-0024C
Signal Computer UPS
DB9F DB9M
RxD 2 -------------------- 2 TxD Send
TxD 3 -------------------- 1 RxD Receive
DCD 1 --*
|
DTR 4 --*
GND 5 -------------------- 9 Ground
RTS 7 --*
|
CTS 8 --*
940-0095A Cable Wiring
Supported
Models:
APC BackUPS Pro PNP
Contributed
by:
Chris Hanson cph at zurich.ai.mit.edu
This is the definitive wiring diagram for the 940-0095A cable submitted by Chris Hanson, who
disassembled the original cable, destroying it in the process. He then built one from his diagram and it
works perfectly.
APC Part# - 940-0095A
UPS end Computer end
------- ------------