BATTDATE [ mm/dd/yy | dd/mm/yy ]
Last battery replacement date. Maximum of 8 characters.
SENSITIVITY [ H | M | L ]
H : High (most sensitive setting) M : Medium L : Low (least sensitive setting)
WAKEUP [ 000 | 060 | 180 | 300 ]
The time delay in seconds that the UPS waits after the return of utility power before "waking up" and
restoring power to the connected equipment.
SLEEP [ 020 | 180 | 300 | 600 ]
The time delay in seconds for which the UPS waits or "sleeps" after it receives a request to power off
the connected system.
LOTRANSFER <voltage>
Low line voltage causing transfer to battery power or activation of SmartBoost. Allowable values
depend on the last letter of the firmware or APCMODEL. Typical values are:
D 106 103 100 097
M 177 172 168 182
A 092 090 088 086
I 208 204 200 196
where D = domestic (USA), M = Canada, A = Asia and I = International.
HITRANSFER <voltage>
High line voltage causing transfer to battery power or activation of SmartTrim. Allowable values
depend on the last letter of the firmware or APCMODEL. Typical values are:
D 127 130 133 136
M 229 234 239 224
A 108 110 112 114
I 253 257 261 265
where D = domestic (USA), M = Canada, A = Asia and I = International.
RETURNCHARGE [ 00 | 15 | 50 | 90 ]
Percentage of battery charge needed for the UPS to restore power to the connected equipment.
BEEPSTATE [ 0 | T | L | N ]
Alarm delay.
0 : Zero delay after power fails.
T : When power fails plus 30 seconds.
L : When low battery occurs.
N : Never.
LOWBATT <minutes>
Low battery warning occurs when the specified number of minutes remains before the UPS estimates
battery power will be exhausted. There are four user-changeable settings: 2, 5, 7, or 10 minutes
OUTPUTVOLTS <voltage>