InRow RD Fluid Cooled Installation18
Leveling the Equipment
Note: The leveling feet at the corners of the equipment provide a stable base if the floor is
uneven, but they cannot compensate for a badly sloped surface.
1. Remove the front and rear doors. See “Door removal” on page 15.
2. For each leveling foot, insert a Phillips PH2 or
slotted screwdriver into the screw above the
leveling foot. Turn the screw clockwise to extend
the leveling foot until it makes firm contact with
the floor.
3. Re-install the front and rear doors.
Note: Use a 13-mm open-ended wrench to level the equipment without removing the
doors.
Stabilizing the Equipment
Floor brackets
To prevent the equipment from moving from its final location (if it is not joined with an enclosure), use
the included bolt-down kit (AR7701). Follow the installation instructions included with the kit.