InRow RD Fluid Cooled Installation24
User interface connections
1
A-Link ports: Pin 1-High; Pin 2-Low;
Pins 3, 6-Perf Power; Pins 4, 5-Ground
<
Alarm NO (normally open contact)
2
Reset button
=
Alarm COM (common contact)
3
Network port
>
Alarm NC (normally closed contact)
4
Shield/ground
?
RS-232 console port
5
A- = True
@
Outdoor heat exchanger (OHE) alarm input -
6
B+ = True
A
OHE alarm input +
7
Shutdown -
B
OHE COM
8
Shutdown +
C
OHE NO
9
24 Vdc (bias)
D
Remote temperature sensor
:
12 Vdc (bias) Leak detector port (AP9325)
;
Return (bias)
OHE
Shutdown input
contacts and alarm
output contacts
Modbus