Operation andMaintenanceInRow™ RDFluid CooledACRD200ACRD201

Page 2 - 동봉된 CD 안에 한국어 매뉴얼이 있습니다

InRow RD Fluid Cooled Operation and Maintenance2Safety Read and adhere to the following important safety considerations when working with this cooling

Page 3

3InRow RD Fluid Cooled Operation and MaintenanceCommissioningWarning: Procedures in this section must be performed by APC authorized personnel.Electri

Page 4

InRow RD Fluid Cooled Operation and Maintenance4Electrical inspection checklistThe electrical inspection verifies that all electrical connections are

Page 5 - Contents

5InRow RD Fluid Cooled Operation and MaintenanceUser interface inspection checklistThe user interface inspection verifies that the sensors and interna

Page 6

InRow RD Fluid Cooled Operation and Maintenance6OperationDisplay InterfaceItem Function1Critical Alarm LED (red) When lit, a critical alarm condition

Page 7

7InRow RD Fluid Cooled Operation and MaintenanceUsing the Display InterfaceEvery time power is applied to the cooling unit, the display interface init

Page 8

InRow RD Fluid Cooled Operation and Maintenance8Navigating the main menuSelector arrow. Press the up or down arrow key to move the selector arrow 1 to

Page 9 - General Information

9InRow RD Fluid Cooled Operation and MaintenanceUsing the Path statementSelect the main- and sub-menu options specified in the path statement to view

Page 10

InRow RD Fluid Cooled Operation and Maintenance10Start the cooling unitPath: Main > Operation> On/Standby1. To start the cooling unit, press the

Page 11 - Commissioning

11InRow RD Fluid Cooled Operation and MaintenanceGeneral ConfigurationThe cooling group configuration options are set during the commissioning of the

Page 12 - Ensure that the:

This manual is available in English on the enclosed CD.Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.Deze handleiding staat in

Page 13 - Final inspection checklist

InRow RD Fluid Cooled Operation and Maintenance12ContactsView the state of input and output contactsPath: Main > Configure Unit > Discrete I/OEa

Page 14 - Operation

13InRow RD Fluid Cooled Operation and MaintenanceCooling Group ConfigurationUse the cooling group configuration settings to add cooling units to the g

Page 15 - Using the Display Interface

InRow RD Fluid Cooled Operation and Maintenance14Availability. Redundancy (Backup Units), Runtime Balancing and Load Assist modes are only supported i

Page 16 - Navigating the main menu

15InRow RD Fluid Cooled Operation and MaintenanceControl the EnvironmentThe primary function of the cooling unit is to capture the heat generated by I

Page 17 - NTER key to select the

InRow RD Fluid Cooled Operation and Maintenance16PID settingsPath: Main > Set Group PIDThe Proportional plus Integral plus Derivative (PID) loop co

Page 18 - Stop the cooling unit

17InRow RD Fluid Cooled Operation and MaintenanceTune the PID loopA qualified service technician must tune the PID loop to optimize the performance of

Page 19 - General Configuration

InRow RD Fluid Cooled Operation and Maintenance18Run hoursThe cooling unit records the number of hours each of its components has operated. When a com

Page 20 - Contacts

19InRow RD Fluid Cooled Operation and MaintenanceDisplay SettingsSet display interface settings including the time and date, units of measure, passwor

Page 21 - Cooling Group Configuration

InRow RD Fluid Cooled Operation and Maintenance20Beeper Volume. Set the volume (Low, Medium, High or OFF) of the audible tone that sounds every time a

Page 22 - Configure Modbus

21InRow RD Fluid Cooled Operation and MaintenanceView Status ReadingsThe display interface has several options for viewing the status of the cooling u

Page 23 - Control the Environment

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Page 24 - PID settings

InRow RD Fluid Cooled Operation and Maintenance22Superheat. The superheat temperature of the compressor . Compressor. The state of the compressor (On/

Page 25 - Tune the PID loop

23InRow RD Fluid Cooled Operation and MaintenanceEvent LogThe event log saves status information and a message each time a change in the cooling group

Page 26 - Service Intervals

InRow RD Fluid Cooled Operation and Maintenance24Alarm messages and suggested actionsAlarm Message Severity Action RequiredCool Fail Critical • A hard

Page 27 - NTER key to confirm

25InRow RD Fluid Cooled Operation and MaintenanceFan PwrSp Fault(Lower Fan Power Supply Fault)Warning • Make sure the power supplies are seated proper

Page 28 - ENTER to

InRow RD Fluid Cooled Operation and Maintenance26Rack Inlet(Rack Inlet Temperature High Threshold)Critical • Make sure the Rack Inlet setting is corre

Page 29 - View Status Readings

27InRow RD Fluid Cooled Operation and MaintenanceNetwork Management CardQuick ConfigurationThe cooling unit is shipped with a Network Management Card

Page 30 - About the cooling unit

InRow RD Fluid Cooled Operation and Maintenance28APC Device IP Configuration WizardYou can use the APC Device IP Configuration Wizard at a computer ru

Page 31 - Event Log

29InRow RD Fluid Cooled Operation and MaintenanceBOOTP. For the Network Management Card to use a BOOTP server to configure its TCP/IP settings, it mus

Page 32

InRow RD Fluid Cooled Operation and Maintenance30DHCP. You can use a RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for the Ne

Page 33

31InRow RD Fluid Cooled Operation and MaintenanceRemote access to the control consoleFrom any computer on the same subnet as the Network Management Ca

Page 35 - Network Management Card

InRow RD Fluid Cooled Operation and Maintenance32Control consoleAfter you log on at the control console, as described in“Local access to the control c

Page 36 - .ini file utility

33InRow RD Fluid Cooled Operation and MaintenanceAccess a Configured Network Management CardOverviewAfter the Network Management Card is running on yo

Page 37

InRow RD Fluid Cooled Operation and Maintenance34Telnet for basic access. Telnet provides the basic security of authentication by user name and passwo

Page 38 - 04) is the length

35InRow RD Fluid Cooled Operation and MaintenanceSimple Network Management Protocol (SNMP)SNMPv1 only. After you add the PowerNet® MIB to a standard S

Page 39

InRow RD Fluid Cooled Operation and Maintenance36Recover From a Lost PasswordYou can use a local computer (a computer that connects to the Network Man

Page 40 - TCP/IP from the Network menu

37InRow RD Fluid Cooled Operation and MaintenanceMaintenanceMonthly Preventive MaintenancePhotocopy the following pages and use them during the mainte

Page 41 - Telnet and SSH

InRow RD Fluid Cooled Operation and Maintenance38MechanicalElectrical Hazard: Turn off the cooling unit, disconnect all power sources, and perform Loc

Page 42

39InRow RD Fluid Cooled Operation and MaintenanceQuarterly Preventive MaintenancePerform all the Monthly Preventive Maintenance items and the items be

Page 43

InRow RD Fluid Cooled Operation and Maintenance40TroubleshootingProblem Possible Cause Corrective ActionControls erratic or inoperative• Inlet temper

Page 44 - Recover From a Lost Password

41InRow RD Fluid Cooled Operation and MaintenanceFluid valve not responsive • Actuator not connected properly• Verify that the actuator is connected p

Page 45

ContentsInRow RD Fluid Cooled Operation and Maintenance iGeneral Information... 1Overview . . .

Page 48 - Troubleshooting

08/2010990-3214A-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Page 49

ii InRow RD Fluid Cooled Operation and MaintenanceCooling Group Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Configure

Page 50

InRow RD Fluid Cooled Operation and Maintenance iiiNetwork Management Card... 27Quick Configuration . . . . . .

Page 52 - 08/2010990-3214A-001

1InRow RD Fluid Cooled Operation and MaintenanceGeneral InformationOverviewNote the definitions for the icons here and be observant for them throughou