APC AP9606 User's Guide Page 41

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 40
Web/SNMP Management SmartSlot Card User’s Guide 41
Device Manager Menus
UPS Control Options
Silcon DP300E
series UPS
Three control actions are available for a Silcon DP300E series UPS.
Note:
Only the
Reset UPS to Defaults
option is available by default.
To enable the turn-off options, do the following:
1. Access the Control Console from a local computer which has a
direct, serial-cable connection with the Management Card, as
described in
Local (serial) access on page 15
.
Note:
You cannot use the Web interface or Telnet access to
the Control Console to enable the turn-off options.
2. Select the
Device Manage
r option from the
Control Console
menu.
3. Select the Silcon DP300E option.
4. Select the
Control
option.
5. Enable the turn-off options.
6. Use C
TRL
-C to return to the
Control Console
menu.
7. Log out to have the change take effect.
You can use the Web interface or Telnet to disable the turn-off options,
but you must use local access to the Control Console to enable them
again.
Continued on next page
Action Definition
Turn UPS Off
Turns the
UPS
off after the expiration of the
Shutdown Delay
described in the table in
Shutdown parameters on page 45
.
Turn UPS Off
Gracefully
Causes the
UPS
to turn off after PowerChute plus has time to
shut down the server’s operating system safely.
Reset UPS To
Defaults
Resets all
UPS
parameters to their default settings.