APC AP9606 User's Guide Page 42

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 41
Web/SNMP Management SmartSlot Card User’s Guide 42
Device Manager Menus
UPS Control Options
continued
Smart-UPS,
Matrix-UPS, and
Symmetra
Power
Array
The Smart-UPS, Matrix-UPS, and Symmetra Power Array
Control
options are identical, with one exception: Symmetra Power Array and
Matrix-UPS use a bypass mode; Smart-UPS does not.
Note:
For information about the
Sleep Time
setting which appears in
the Web interface’s “Control” and “Configuration” pages, see
the table in
Shutdown parameters on page 45
.
With one exception, control actions are accessed through the
Control
menu in the Web interface and the Control Console. The
Reset UPS To
Defaults
is a
Configuration
menu option in the Control Console.
Note:
Use the
Control
menu in the Control Console to access the
diagnostic tests which are accessed through the
Diagnostics
option in the Web interface. For descriptions of the
Self-Test
,
Simulate Power Failure
,
Start/Stop Runtime Calibration
, and
Test UPS Alarm
options, see
UPS Diagnostics Options on
page 40
.
Action Definition
Turn UPS On
Turns the
UPS
on.
Turn UPS Off
Turns the
UPS
off after the
Shutdown Delay
described in the
table in
Shutdown parameters on page 45
.
Turn UPS Off
Gracefully
1
Causes the
UPS
to turn off after PowerChute plus has time to
shut down the server’s operating system safely.
Reboot UPS
Reboots the attached equipment by immediately causing the
UPS
to turn off and then back on again.
Reboot UPS
Gracefully
1
Reboots the attached equipment by causing the
UPS
to turn
off and then back on again, after PowerChute plus has time to
safely shut down the server’s operating system.
Put UPS To Sleep
Turns the
UPS
immediately off for the period of time defined by
the
Sleep Time
setting described in the table in
Shutdown
parameters on page 45
.
Put UPS To Sleep
Gracefully
1
Turns the
UPS
off for the period of time defined by the
Sleep
Time
setting described in the table in
Shutdown parameters
on page 45
, after PowerChute plus has time to safely shut
down the server’s operating system.
Put UPS In/Take
UPS Off Bypass
Controls the use of bypass mode, which allows some
maintenance to be performed at a Matrix-UPS or Symmetra
Power Array model without turning off the
UPS
.
Reset UPS To
Defaults
Resets all
UPS
parameters to their default settings.
1
For information about the
Low-Battery Shutdown
parameter that defines how
much time PowerChute plus has available to shut down the server safely, see the
table in
Shutdown parameters on page 45
.