APC AP9606 Specifications Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
12 Implementing UPS Configurations with Microsoft Cluster Server
2.2.1.1 Battery source
The battery source is comprised of parallel, hot-swappable, 120 V battery
modules. These are housed in the Symmetra frame, and in an optional XR
Extension Battery frame. A Symmetra Miniframe provides bays for up to two
battery modules, and a Masterframe provides bays for up to four. Both of these
frames can be connected to an XR Extension Battery frame. Additional battery
modules increase battery run time.
2.2.1.2 Control
Symmetra incorporates a main intelligence module (MIM) that continuously
monitors the system. The MIM does the following:
Coordinates the initial startup of the system
Transfers it into and out of bypass mode
Transfers the power source between the main AC power and the battery
source
Coordinates shutdown operations
Gathers data about the system components
Delivers it to the Powerview interface and the computer interface ports
System status monitoring and reporting data includes the current predicted run
time, the status of individual battery and power modules, the size of input and
output voltage, the input and output voltage frequency, and the size and status of
the output load.
2.2.1.3 Alarm condition detection
The control/user interface system monitors Symmetra for alarm conditions. If an
alarm condition is detected, the Powerview user interface initiates an audible and
visual alarm. Alarm conditions include on-battery, low battery, module faults,
overloads, loss of redundancy and a variety of other default and user-defined
events.
More information is available at:
http://www.apcc.com/products/symmetra/index.cfm
2.2.1.4 VA ratings
The Symmetra comes in different VA ratings:
Miniframe: 4 - 8 kVA
Masterframe: 8 - 16 kVA
(always + one 4 kVA power module for N+1 redundancy)
Page view 19