66 Implementing UPS Configurations with Microsoft Cluster Server
Clear the check in the Run Command File checkbox.
We strongly recommend that you do not start the cluster automatically. An
administrator has to evaluate the situation and take the required
measurements. Besides, it is mandatory to start the systems in a data center
in a certain order (PDC, BDC, databases, etc.). Usually the MSCS is the last
component to start.
Figure 70. Double UPS Run Command File Comm Lost While On Battery
11.In the Event Actions window, select Comm Lost While On Battery.
a. Select the Run Command File checkbox and click Options.
b. In the pop-up window, insert the following in the Command File field:
“C:\UPS_CMD\UPS.CMD” UPSOnBattery >> C:\UPS_CMD\LOG.TXT
c. Set the Wait value to 0 seconds. If the UPS is on battery and
communication is lost, an immediate action is required because the state
and run time of the UPS are unknown.