Chapter 2. APC hardware and software background 21
Comm Lost While On Battery
Communication with the UPS has been lost while the UPS is on battery. The
event may be caused by a loose communication cable or, rarely, by a software
conflict, such as an application inadvertently blocking PowerChute PLUS from
monitoring the serial port while the UPS is on battery.
RECOMMENDED ACTION: Run the command file UPS.CMD to either move
or set the Cluster Groups offline. This script is described in Chapter 4, The
command file UPS.CMD on page 67.
PowerChute PLUS Started
PowerChute PLUS UPS monitoring has been started.
RECOMMENDED ACTION: None. After a shutdown, the cluster should be
brought back online manually by the Administrator.
UPS Battery Is Discharged
The UPS is online, but its battery capacity is low. If power fails, PowerChute
PLUS shuts down the system immediately.
RECOMMENDED ACTION: Immediately notify the cluster administrator. Use
the notify function that was implemented in PowerChute PLUS.
Lost Communication With UPS
PowerChute PLUS attempts to establish communication with the UPS and
fails, or communication that was established is lost.
RECOMMENDED ACTION: Immediately notify the cluster administrator. Use
the notify function that was implemented in PowerChute PLUS.
UPS Output Overload
For an APC UPS, the equipment load on the UPS exceeds its rated load
capacity. Reduce the load by unplugging some equipment from the UPS, and
run a self-test.
A Smart-UPS will sound an alarm when loads greater than 107% of its rating
are applied for more than approximately four seconds. Sustained overloads
greater in amplitude than 107% may cause the UPS's input circuit breaker to
trip, depending on the level of overload and its duration. In this case, the UPS
will shut down and not attempt to transfer to battery power in order to protect
its internal circuitry. Note: an overload is detected and indicated independent
of line voltage at 107% of full rated load for all models.
When operating on-battery, the UPS will not attempt to support steady-state
overloads and will shut down after approximately two to five seconds of their
application. However, transient overloads applied while on-battery and lasting
less than one second will be supported up to 150% of the UPS's load rating. In
this case, the output voltage may not be within the specified regulation limits.
The likelihood of the UPS shutting down while operating on-battery due to
transient overload above this rating is increased as the battery becomes
discharged during an extended power outage.
RECOMMENDED ACTION: Immediately notify the cluster administrator.
Battery Needs Replacing
One or more UPS batteries are heavily discharged and can no longer hold a
full charge. If utility power fails during this condition, an APC runs for less than
half its normal run time.