Page view 20
Chapter 2. APC hardware and software background 13
APC part numbers:
SY4KEXI Miniframe with 1 PM (4 kVA) expandable to 8 kVA redundant
SY8KI Miniframe with 2 PM (8 kVA) expandable to 8 kVA redundant
SY8KEXI Masterframe with 2 PM (8 kVA) exp. to 16 kVA redundant
SY12KEXI Masterframe with 3 PM (12 kVA) exp. to 16 kVA redundant
SY16KI Masterframe with 4 PM (16 kVA) exp. to 16 kVA redundant
SYPM Additional power module
SYBATT Additional battery module
SYXR4 Extended battery frame for up to 4 modules (not included)
SYXR12 Extended battery frame for up to 12 modules (not included)
You can find the IBM part numbers in Appendix C of the IBM Paper Configurator.
This document is available from http://www.pc.ibm.com/support/.
Table 7. Run time chart
UPS Intelligent Battery Battery
UPS Battery Battery Battery
UPS Intelligent UPS Battery Battery Battery
UPS Battery UPS Battery Battery Battery
UPS Battery UPS Battery Battery Battery Battery Battery
Power Power Battery Battery Battery Battery
8 kVA 16 kVA Extended Battery Extended Battery
31”H x 24”W x 27”D 45”H x 24”W x 27”D 18”H x 24”W x 27”D 46”H x 24”W x 27”D
SYMINI SYMSTR SYXR4 SYXR12
VA load Number of batteries installed
1234567891012
2000
15 40 66 96 126 162 192 222 258 288 354
3000
9 23 40 58 78 96 120 138 156 180 222
4000
615274053668496114126156
5000
n/a112029405162728496120
6000
n/a 9 15 23 31 40 49 58 66 78 96
7000
n/a 7 12 18 25 32 40 47 55 60 79
8000
n/a 6 10 15 21 27 33 40 46 53 66
9000
n/an/a9 1318232834404658
10000
n/an/a7 1115202429344051
12000
n/a n/a 6 9 12 15 19 23 27 31 40
14000
n/a n/a n/a 7 10 12 15 18 22 25 32
15000
n/a n/a n/a 6 9 11 14 17 20 23 29
16000
n/an/an/a6 8 101315182127