20 kVA - 80 kVA UPS
Users and Installation Manual
1015543
Revision D
11
Avoid temperature and humidity extremes. To maximise the life time of the batteries, an
ambient temperature of 15°C to 25°C is recommended.
Provide shelter from the elements (especially moisture)
Make sure that ventilation and space requirements are met. When the UPS is in use, there
should be 10 mm clearance on the left side and 150 mm on the right side of 20-30 kVA
UPS and 10 mm on the right side of 40-80 kVA UPS. 250 mm clearance is needed at the
rear of the UPS and 500 mm on top of the UPS for ventilation, see figures 4a and 4b.
1000 mm clearance is needed in the front of the UPS for servicing.
Maintain clearance at front of the UPS for service and user operations.
The extra battery is preferred to be installed next to the UPS.
Figure 4a. Ventilation and space requirements for 20 - 30 kVA UPS.
Figure 4b. Ventilation and space requirements for 40 - 80 kVA UPS.
6. Installation
6.1 Environment
All the requirements concerning environment described in this chapter (Installation) or chapter
11 (Technical specifications) must be met. If they are neglected the manufacturer cannot
guarantee the safety of personnel during installation or use, or that the unit will function properly.
When locating the UPS system and the battery options, the following points have to be remembered: