6.4 Installing 40 - 80 kVA UPS and battery cabinets
External battery cabinets should be installed on the left side of the UPS. The cabinets should
be bolted together by using the metal plates provided with external battery cabinets.
See figure 6a.
Before connecting UPS and battery cabinets together the left side plate of the battery cabinet
have to be removed. Do not remove the UPS cabinet side plates.
When connecting battery cabinets together with the connection plates delivered with
battery cabinets (figure 6a) remove both side plates between the cabinets.
Each battery cabinet has temperature measurement and the cable from battery cabinet has
to be connected to terminal X6 (male) beside the input/output terminals. See figure 8. Cable
routing is under the cabinets. When several external cabinets are used the temperature
information from battery cabinets has to be linked together. See figures 6b and 6c. The
temperature sensor is located under the roof of the battery cabinet.
Cabling between UPS and battery cabinet is done through lower part of UPS right side. If
connecting several D and E battery cabinets the cabinet connections should be according
figure 6b. Battery connections with battery cabinet F should be done according figure 6c.
Figure 6a. Connecting battery cabinet to 40-80 kVA UPS module. (Right side panels of
battery cabinets disconnected)