The UPS unit has the following power connections:
3-phase and N and
connection for rectifier input
3-phase and N and
connection for bypass input
3-phase and N and
connection for load output
+, -, N and PE connection for external batteries
All input and output wiring of the UPS connects to the terminals located behind the cover
plate behind the door and the front panel. Wiring can be routed through the cable entry at
the bottom or back of the UPS cabinet.
The UPS is provided with a single phase 230 V power supply for use with internal modem or
portable computer. Connection is at terminal X5. This power supply is protected with an
automatic 10 A fuse F3. See figure 7 or figure 8 according to UPS power.
The UPS is provided with temperature sensor connections for the optional isolation
transformer and input filter. Terminal X7 is for the transformer and terminal X12 is for the
input filter. These terminals are located beside the input/output terminals. See figure 7 or 8. For
more information see the installation instruction of the transformer or input filter option.
Figure 7. 20-30 kVA UPS connection locations