20 kVA - 80 kVA UPS
Users and Installation Manual
1015543
Revision D
34
Going to the bypass mode
Before going to bypass made check from the display that the unsychronised alarm is not active.
Press “Menu” button and see the UPS status by pressing
button.
Turn the maintenance bypass switch into the ‘Bypass’-position.
Going to the Service mode (only in 40-80 kVA UPSes)
Shut down the UPS according shutting down procedure in chapter 8.2.
Turn the maintenance bypass switch to the ‘Maintenance’ position.
Returning to normal mode
If the maintenance bypass switch is in ‘Maintenance’ position (only in 40-80 kVA UPSes)
turn the maintenance bypass switch into the ‘Bypass’ position.
Start up the UPS according start up instructions in chapter 8.1.
9. Maintenance
All operations inside the unit must be carried out only by a service engineer from the
manufacturer or from an agent, authorized by a manufacturer.
Battery maintenance
The condition of the batteries is crucial to correct operation of the UPS. The UPS units are
provided with the automatic battery test ABM, which continuously controls the condition of
the battery bank. When the capacity of the battery bank has decreased remarkably, the UPS
will indicate this by audible and visual alarms.
In addition to the automatic battery test it is recommended that a battery discharge test is
done once or twice per year. This test is recommended to be done together with the preventive
maintenance by service engineer from the manufacturer of by an agent authorised by the
manufacturer.
Scrapping the UPS
Before scrapping UPS or its battery cabinet, battery bank and the lithium battery on the logic board
must be removed. Due to high energy and high voltage, removal of batteries is allowed only for
authorised service personnel. Local requirements must be followed in battery recycling or discard.
WARNING!
HAZARDOUS MATERIALS. Batteries may contain HIGH VOLTAGES,
and CAUSTIC, TOXIC and FLAMMABLE substances. Batteries can injure or kill people
and damage equipment if used improperly. DO NOT DISCARD unwanted batteries or
battery material in the public waste disposal system. Follow ALL applicable, local
regulations for storage, handling and disposal of batteries and battery materials.
10. Warranty
The product is warranted against defects in material and workmanship for a period of 12
months from its original date of purchase.