APC DCM00K02W483 Datasheet Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
User Manual 990-9178A
DC MX06 40A Shelf Page 12 of 44 18
th
FEB 02
2.3 Controller
2.3.1 Alarm Card Layout
Part Reference Function Adjustment
P1
Output Volts Adjust Via Front Panel
P2
LVD Disconnect Volts Adjust Factory Pre-set
P3
Meter Current Calibration Factory Pre-set
P4
Meter Reading Zero Adjust Factory Pre-set
P5
Meter Volts Calibration Factory Pre-set
SK1
Link Pins 1+2 (27V), 2+3 (54V) (Temp Compensation) Factory Pre-set
SK2
Link Pins 1+2 (27V), 2+3 (54V) (LVD Coil) Factory Pre-set
SK3
Link Pins 1+2 (27V), 2+3 (54V) (LVD Circuit) Factory Pre-set
SK4
Optional front panel access to signals N/A
SK5
Link Pins 1+2 (27V), 2+3 (54V) (Voltage Programming) Factory Pre-set
SK7
Link Pins 1+2 (27V), 2+3 (54V) (Meter Current) Factory Pre-set
SK10
Link Pins 1+2 (Temp Comp), 2+3 (Non Comp) Factory Pre-set
SK11
Main 64 Pin Connector N/A
SW1
Battery connection (LVD) “ON”, “AUTO” or “OFF” Via Front Panel
SW2
Selects any of 11 alarms to give a “MAJOR” alarm Remove Controller
SW3
Battery Test function (press and hold for test) Via Front Panel
SW5
Selects any of 11 alarms to give a “MINOR” alarm Remove Controller
SW6
Selects “Volts” or “Amps” reading for LED meter Via Front Panel
LED Meter
Optional 3½ digit LED Display N/A
SW1
SW6
P5
P4
P3
P2
P1
SK11
SK4
LED
Meter
SW2SW5
SK10
SW3
SK1
SK7SK2SK3
112 1
1
12
11
1
32
1
1
SK5
1
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 43 44

Comments to this Manuals

No comments