User Manual 990-9178A
DC MX06 40A Shelf Page 25 of 44 18
th
FEB 02
4.1.1.2 Front Access Connection
To connect the input supply to the MX06 40A Shelf proceed as follows:
• The same protection devices and cable parameters are required for front access connection
as explained for “single-phase rear access” previously.
• Ensure that the AC supply intended for connection is isolated, locked off and under single
operator control.
• Strip the ends of the AC Input cables to be connected to the Input terminal block.
• By unscrewing the 2 front panel screws the AC Input connection drawer can be opened as
shown below. The AC Input cable is fed through the gland and screwed into the terminal
block visible.
• Connect as follows: Safety earth to position marked with earth symbol (connect first)
Live to AC1
Neutral to AC2
• The alarm card adjacent to the AC Input drawer may need to be removed for easier access
to the terminal block screws.
• A strain relief bush can be fitted instead of the standard cable gland shown. Contact factory
for details.
Cable Gland
Terminal Block