4.1.1.2 Front Access Connection
To connect the input supply to the MX06 40A Shelf proceed as follows:
The same protection devices and cable parameters are required for front access connection
as explained for “single-phase rear access” previously.
Ensure that the AC supply intended for connection is isolated, locked off and under single
operator control.
Strip the ends of the AC Input cables to be connected to the Input terminal block.
By unscrewing the 2 front panel screws the AC Input connection drawer can be opened as
shown below. The AC Input cable is fed through the gland and screwed into the terminal
block visible.
Connect as follows: Safety earth to position marked with earth symbol (connect first)
Live to AC1
Neutral to AC2
The alarm card adjacent to the AC Input drawer may need to be removed for easier access
to the terminal block screws.
A strain relief bush can be fitted instead of the standard cable gland shown. Contact factory
for details.
Cable Gland
Terminal Block