User Manual 990-9178A
DC MX06 40A Shelf Page 34 of 44 18
th
FEB 02
4.2.3 4 Circuit Breakers Rear Access
Remove the rear cover to give access to the output terminals (shown below).
To connect to the output terminals use M4 ring crimps with cables rated to at least the same
current rating as the corresponding output breaker and colour coded as to meet all the local
installation regulations.
No. of Outputs :
4
Output Rating :
4 O/P’s up to 20A max
2 O/P’s up to 40A max
1 O/P up to 50A max
Circuit Breakers :
Series DC Current trip,
Medium time delay.
Trip Alarm :
YES
Output 1
Distributed Output 1
Distributed Output 4
Output 4
Top 4 Terminals :
0V / Earth, when output earthed
Bottom 4 Terminals :
+ 54Vdc when negative earth
- 54Vdc when positive earth
Cables should be routed through
knockout panels in rear cover or in
the side of the shelf itself.