APC DCM00K02W483 Datasheet Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
User Manual 990-9178A
DC MX06 40A Shelf Page 18 of 44 18
th
FEB 02
2.5.5 Temperature Compensation
Input Description Socket Pin
Temp Compensation
This function allows a temperature probe to be used to
automatically adjust the output voltage of the system. This
ensures the charging voltage stays within the battery
manufacturers recommended limits. To connect thermistor,
simply enter striped wires into SK19 and screw to clamp
(polarity not important). Check controller configuration link
as explained below.
Note: See page 14 for SK19 location photo
SK19 1 - 2
System Controller
Link fitted on top
2 pins for Temp
Comp
Link fitted on
bottom 2 pins for
no compensation
(fixed o/p Volts)
ALARM CARD
MX06 40A Calculated Temperature Compensation (54V)
52.00
53.00
54.00
55.00
56.00
57.00
58.00
59.00
-10.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00 70.00
Temperature (°C)
Voltage (V)
Output Voltage max
Output Voltage nom
Output Voltage min
Minimum Battery Voltage
Maximum Battery Voltage
Page view 17