Page view 31
User Manual 990-9178A
DC MX06 40A Shelf Page 32 of 44 18
th
FEB 02
4.2 DC Distribution
The MX06 40A Shelf has a DC distribution module fitted. This module contains the chosen distribution
components of either circuit breakers or fuses. It also contains an LVD contact (controlled by the controller)
and a current shunt measuring load current. The modules can be configured for either positive or negative
earthed output. The output can also be left floating to facilitate external grounding. A tripped output will give
an alarm displayed as a front panel LED.
There are three standard distribution component types:
1/ 10 GMT Fuses
2/ 4 Cartridge Fuses
3/ 4 Circuit Breakers
As explained earlier all three types are offered with either front or rear cable access giving six modules
types.
4.2.1 10 GMT Fuses Rear Access
No. of Outputs :
10 max
Output Rating :
10A max per output
(42A total)
Fuses :
GMT-** (Bussmann)
Trip Alarm :
YES
Cables should be rated to at least the same
current rating as the corresponding output fuse
and be colour coded as to meet all the local
installation regulations.
To attach the cables remove the rear cover fo
r
access to output connectors.
Simply strip the ends of the cables and screw into
output terminal block.
Output 1
Distributed Output 1
Distributed Output 10
Output 10
Top Connector :
Common (0V Return) / Earth (if link fitted)
Bottom Connector :
- 54Vdc (when positive earthed)
DISTRIBUTION
FUSES
1
2
3
4
5
6
7
8
9
10