SURT15k/20k 230 VAC Stack/Rack-Mount 6U XLI/XLICH/XLI-CC10
Wiring Specifications
Adhere to national and local electrical codes when wiring.
*Terminal screw tightening torque: 4.5 Nm (40 lb-in) minimum
**Use cables and input circuit breakers rated for specifications listed in these tables.
NOTE: Units configured for three phase input and single phase output operation, the entire load connected to the
UPS will transfer to L1 and Neutral of the three phase input when the UPS is operating in Bypass mode.
***The current is specified at nominal input voltage.
The acceptable input frequency range is 40 Hz to 70 Hz.
The output frequency is user selectable. Refer to the PowerView display menu screens for available options.
Input Connections Output Connections
Main Input
Single-Phase: Wire to L1, N, and
Three-Phase: Wire to L1, L2, L3, N, and
Hardwire
Single-Phase: Wire to L1, N, and
Three-Phase: Wire to L1, L2, L3, N, and
Bypass Input (optional)
Single-Phase: Wire to B1, N, and
Three-Phase: Wire to B1, B2, B3, N, and
Single-phase PDU
XL battery pack PDU to UPS: Wire L1, N,
Single Feed
Wiring
Number
of
Phases Voltage
Current
Full Load***
(maximum)
External Input
Circuit Breaker
(typical)
Wire Size
(typical)*
SURT15K XLI/XLICH/XLI-CC
Input
Output
1
1
220/230/240 VAC
220/230/240 VAC
83 A
66 A
100 A each phase
not required
35 mm
2
25 mm
2
Input
Output
3
1
380/400/415 VAC
220/230/240 VAC
28 A each phase
66 A
100 A each phase**
not required
35 mm
2**
25 mm
2
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
28 A each phase
22 A each phase
35 A or 40 A each phase
not required
6 mm
2
6 mm
2
SURT20K XLI/XLICH/XLI-CC
Input
Output
1
1
220/230/240 VAC
220/230/240 VAC
105 A
87 A
125 A each phase
not required
50 mm
2
35 mm
2
Input
Output
3
1
380/400/415 VAC
220/230/240 VAC
35 A each phase
87 A
125 A each phase**
not required
50 mm
2**
35 mm
2
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
35 A each phase
29 A each phase
50 A each phase
not required
10 mm
2
10 mm
2