SURT15k/20k 230 VAC Stack/Rack-Mount 6U XLI/XLICH/XLI-CC 23
Troubleshooting Display Messages
Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com
for assistance with complex UPS problems.The PowerView reports various messages on the display, including
alarm status and changes in system configuration. This section lists all the PowerView display messages, the reason
for the message, and the appropriate corrective action.
Messages may occur simultaneously. If this happens, be sure to review all of the messages for a better
understanding of the system condition.
Condition
PowerView Display
Message Reason for Message Corrective Action
Start-Up #Batteries changed since
last ON.
At least one battery module has been
added or removed from the UPS since the
last time the Pwr ON command was
issued.
No corrective action necessary. Proceed
with the start-up.
Automatic Self Test
Started.
The UPS has started pre-programmed
battery test.
Batt capacity less than
Return Batt Cap.
The battery capacity of the UPS is less
than the user-specified minimum battery
capacity required to turn on the load.
Option 1) Abort the start-up and
allow batteries to recharge.
Option 2) Continue start-up, with less
than minimum battery capacity.
System Start-Up
Configuration Failed.
System configuration error: Start-up
diagnostic fault.
Check for other alarms.
If the problem persists contact APC
Customer Support. Refer to Contact
Information in this manual.
Mains: Site Wiring Fault Input and Output Jumpers are not
configured correctly
Check input wiring tray jumpers and
output shorting jumper for compatibility.
Refer to the Input/Output Jumper
Configurations table in this manual.
Bypass Not Available -
Wrong Ph Seq
Check bypass jumpers in input wiring
tray and output shorting jumper for
compatibility. Check bypass phases for
positive sequence. Refer to the Input/
Output Jumper Configurations table in
this manual.
Bypass: Site Wiring Fault Check bypass jumpers in input wiring
tray and output shorting jumper for
compatibility. Refer to the Input/Output
Jumper Configurations table in this
manual.
General Status # of batteries increased. At least one battery pair has been added
to the system.
No corrective action is necessary.
# of batteries decreased. At least one battery pair has been
removed from the system.
# External Battery Packs
increased.
At least one external battery pack has
been connected to the UPS.
# External Battery Packs
decreased.
At least one external battery pack has
been disconnected from the UPS.
Module Failure Bad Battery Pair. A battery pair has failed and requires
replacement.
Refer to battery pair installation in the
external battery pack user manual.