SURT15k/20k 230 VAC Stack/Rack-Mount 6U XLI/XLICH/XLI-CC 15
Output wiring options
Output wiring overview. Refer to the diagrams on the following pages for output wiring options.
Labeled jumpers and connectors must be installed in the appropriate locations.
N
OSJ
L3 L2 L1
suo0682a
Neutral
Ground
Output Phase 2
Output Phase 1
Output Phase 3
PDU Terminals
Factory Default Configuration
Output Shorting Jumper (OSJ)
for single phase output
OSJ
N
L3
L2 L1
suo0683a
N
L3
L2 L1
suo0684a
Output hardwire option 1
Single phase hardwire output
connection
Output hardwire option 2
Three phase hardwire output connection
XLBP PDU not connected
Output shorting jumper (OSJ) removed
Ensure the OSJ is
secured to the output
wiring tray using the
five screws provided.