USERS GUIDE
masterswitch plus
13
Watchdog Features
Overview
To detect internal problems and recover from unanticipated inputs, the unit
uses internal, system-wide watchdog mechanisms. When it reboots itself to
recover from an internal problem, a System: Warmstart event is recorded in
the Event Log.
Network interface watchdog mechanism
The unit implements internal watchdog mechanisms to protect itself from
becoming inaccessible over the network. For example, if the unit does not
receive any network traffic for 9.5 minutes (either direct traffic, such as
SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP]
request), it assumes that there is a problem with its network interface and
reboots itself.
Resetting the network timer
To ensure that the unit does not reboot if the network is quiet for 9.5
minutes, the unit attempts to contact the Default Gateway every 4.5
minutes. If the gateway is present, it responds to the unit, and that response
restarts the 9.5-minute timer. If your application does not require or have a
gateway, specify the IP address of a computer that is running on the
network most of the time and is on the same subnet. The network traffic of
that computer will restart the 9.5-minute timer frequently enough to prevent
the unit from rebooting.