APC AP9617 User Manual Page 48

  • Download
  • Add to my manuals
  • Print
  • Page
    / 104
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 47
®
USER’S GUIDE
network management card
46
Control Console. From Device Manager, type 1 to select DC Power
Plant, then type
1 again to select DC System. The following options are
displayed.
1- DC System Parameters
2- OEM Parameters
From the DC System menu, type 1 to select DC System Parameters,
which displays the following menu items:
Menu Item Description
1- Description1 Descriptions related to your DC Power Plant system.
Maximum per field: 16 characters.
2- Description2
3- Description3
4- High
Temperature
The ambient high temperature threshold.
Minimum: 0 ° Celsius
Maximum: 100.00° Celsius
5- High
Temperature
Alarm
The alarm action to occur when the ambient high temperature
threshold (item 4 above) is violated.
Allowed values: any standard alarm selection.
a
6- Low
Temperature
The ambient low temperature threshold.
Minimum: – 100.00° Celsius
Maximum: 100.00° Celsius
7-
Low
Temperature
Alarm
The alarm action to occur when the ambient low temperature
threshold (item 6 above) is violated.
Allowed values: any standard alarm selection.
a
a
Standard alarm selections
Major activates the major relay.
Minor activates the minor relay.
Relay 1 through Relay 6 activates the relay specified.
Ignore ignores the alarm.
Page view 47