From the DC System menu, type 2 to select OEM Parameters, which
displays the following calibration parameters, which are set at the factory
and cannot be changed:
8- Hardware
Temperature
Alarm
The alarm action to occur in response to any of the following
• No temperature probe cable is connected
• A faulty temperature probe cable is connected
• The temperature probe itself is faulty.
This alarm action occurs only if temperature compensation is
enabled. See Battery Thresholds.
Allowed values: any standard alarm selection.
a
9- Remote
Configurability
Disables remote write access to the DC Power Plant. You can re-
enable access only from the DC Power Plant’s front panel.
Accept Changes Use this option to save your changes.
Menu Item Description
Rectifier Offset Rectifier offset adjustment in volts.
Rectifier Gain Rectifier measurement gain adjustment.
Converter
Offset
Converter offset adjustment in volts.
Converter Gain Converter measurement gain adjustment.
Shunt Offset Battery shunt offset adjustment in amps.
Shunt Gain Battery shunt measurement gain adjustment.
Menu Item Description
a
Standard alarm selections
Major activates the major relay.
Minor activates the minor relay.
Relay 1 through Relay 6 activates the relay specified.
Ignore ignores the alarm.