Page 18 - 34003602EN/AB
2. Installation
2.6 Setting up the RS485 link
General
For UPSs equipped with the PowerServices TelPac external version (see table section 2.3 "The various installation
types"), communication between the UPS and the external unit is achieved via a RS485 link in 2-wire mode.
The link works using the master-slave mode, with the PowerServices TelPac always being the master.
Standard practice is to add line bias at the network master and impedance matching at the end of the line on the slave
side.
The line must only be biased at one point.
The external unit is pre-configured to be directly operational. No special configuration is necessary for a "Single-unit" type
installation of the external unit with a Galaxy or Comet type UPS.
Configuration of communication parameters (mode, rate, etc.) is carried out on the RS485 cards on the respective UPSs
(see "Configuring the RS485 card for Comet" or "Configuring the RAUZ card for Galaxy").
"Single-unit" type installation
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
!
!
f
a
u
l
t
The RS485 shielded 2-wire link
Slave number x
Without bias
With impedance matching
1200,8,N,1
Master
With bias
Without impedance matching
1200,8,N,1
UPS with JBUS/
RS485 card
PowerServices
Telpac