2. Installation
PowerServices TelPac external unit (2 inputs + 4 extensions)
Four similar inputs C, D, E, F are available
inside the external unit on terminal block
XM13.
To connect contacts to these four inputs,
proceed as follows:
Remove the cover (partly unscrew the
screws and pivot the cover).
Remove the card from the external unit (3
screws).
Feed the cable through the grommet.
Connect the cable(s) to terminal block
XM13 as shown in the figure opposite.
Replace the card in the external unit and fix
it in place (3 screws).
Replace the cover.
PowerServices TelPac is now ready for the
parameter setting stage required for
Teleservice. Consult the Technical Support
documentation. Lastly, move on to step 2
(see section 2.1 "Procedure").
Extension
C
D
E
F
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
A
B
5V
< 10m
Terminal block
XM13