CHAPTER 4: MESSAGES
18
PowerView
Message
Meaning Corrective Action
Redundancy is
below alarm
threshold.
Actual power module redundancy has
fallen below the user specified
redundancy alarm threshold. Either
power module(s) failed or the load has
increased.
Option 1: If possible, install
additional power modules.
Option 2: Decrease the load.
Option 3: Use the
PowerView to decrease the
redundancy alarm threshold.
(Startup>Setup>Alarms>
Redundancy)
Threshold
Alarm
(continued)
Runtime is below
alarm threshold.
The predicted runtime is lower than
the user specified for the minimum
runtime alarm threshold. Either the
battery capacity has decreased or the
load increased.
Option 1: Allow the battery
modules to recharge.
Option 2: If possible,
increase the number of
battery modules.
Option 3: Decrease the load.
Option 4: Use the
PowerView to decrease the
minimum runtime alarm
threshold.
(Startup>Setup>Alarms>
Runtime)
Bypass is not in
range (either freq
or voltage).
The frequency and/or voltage are out
of acceptable range for bypass. This
message occurs when the UPS is
online and indicates that the bypass
mode may not be available if required.
The system may start
on-battery.
Option 1: Decrease the
sensitivity to input frequency.
(Startup>Setup>OutputFreq)
Option 2: Correct input
voltage to provide
acceptable voltage and/or
frequency.
Bypass contactor
stuck in bypass
position.
The UPS is positioned in the bypass
position and cannot go on-line.
Bypass contactor
stuck in on-line
position.
The UPS is positioned in the on-line
position and cannot go to bypass.
UPS in bypass
due to internal
fault.
The UPS has transferred to bypass
mode because a fault has occurred.
Call your contract service
provider or APC Technical
Support.
UPS in bypass
due to overload.
The load exceeded the system power
capacity. The UPS has switched to
bypass mode.
Option 1: Decrease the load.
Option 2: If possible, add
power modules to the
system.
Bypass
System is in
Maintenance
Bypass.
The UPS is in bypass because the
maintenance bypass switch is in the
On position.
No corrective action
necessary.