CHAPTER 4: MESSAGES
19
PowerView
Message
Meaning Corrective Action
On Battery. The UPS is in the on-battery mode.
The battery modules are being
discharged.
No corrective action is
necessary.
Note: Runtime is limited in
duration. Prepare to
shutdown the UPS and the
load equipment, or restore
incoming voltage.
Need Bat
Replacement.
One or more battery modules are in
need of replacement.
Refer to module
replacement procedure.
UPS Fault. A fault occurred in a power module.
The UPS Fault message always
occurs when there is a bad power
module failure message.
Call your contract service
provider or APC Technical
Support.
Shutdown or unable
to transfer to Batt due
to overload.
The UPS has shutdown because
an overload occurred and bypass is
not available.
Option 1: Reduce the load
to eliminate overload.
Option 2: If possible, add
power modules to eliminate
overload.
Option 3: Replace failed
power modules to eliminate
overload.
Note: If bypass is not
available because of a
power failure, wait for power
to be restored. If there is a
utility problem, have it
corrected.
Load Shutdown from
Bypass. Input
Freq/Volts outside
limits.
The UPS shut the load down while
it was on bypass, because the input
power went out of acceptable
range.
Correct the input voltage
problem.
Fault, Battery Charger
Failure.
The battery charger in one or more
power module(s) failed.
Refer to module
replacement procedure.
Fault, Bypass Relay
Malfunction.
The bypass relay has
malfunctioned.
Call your contract service
provider or APC Technical
Support.
General
Fault
Fault, Internal Temp
exceeded normal
limits.
The temperature of one or more
battery modules is too hot.
Replace overheated
module. Refer to module
replacement procedure.