7Symmetra MW II with External Bypass Static Switch Operation Manual - 990-1377E-001
Operation
Operation Modes
Normal operation
During online operation, the critical load is supported by the inverters. While the UPS system is
operating in this mode, a single-line diagram will appear on the screen. The green line indicates the
power flow from the utility, through the UPS, and then to the load.
Battery operation
During battery operation, the critical load is supported by the inverters. The main inverter is supplied by
battery power, ensuring uninterrupted support to the load. While the UPS system is operating in battery
operation, a single-line diagram will appear on the screen. The green line indicates the power flow from
the batteries, through the main inverters, and then to the load.
Battery
Main Inverter
Delta Inverter
External Bypass SSW
External Bypass SSW
Battery
Delta Inverter
Main Inverter