Apc 3000T User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 33
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
990-7031D, Revision 5 5/01
11
Storage
Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for
at least two hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer
interface port to avoid unnecessarily draining the battery.
Extended storage
At -15 to +30 °C (+5 to +86 °F), charge the UPS’s battery every six months.
At +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every three months.
Replacing the Battery
This UPS has an easy to replace hot-swappable battery. Battery replacement is a safe procedure, isolated from electrical
hazards. You may leave the UPS and loads on for the following procedure. See your dealer or call the number listed under
APC Contact Information, page 21, for information on replacement battery cartridges.
Note:
Please read the cautions in the Safety section at the beginning of this User’s Manual.
Once the battery is disconnected, the loads are not protected from power outages.
Model Number Replacement Battery Cartridge (RBC) #
SU1400XLTNET RBC 11
SU2200XLTNET RBC 11
SU3000TNET RBC 11
SU5000T RBC 12
SU1400RMXLTNET RBC 11
SU2200RMXLTNET RBC 11
SU3000RMT3U RBC 12
SU5000RMT5U RBC 12
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 32 33

Comments to this Manuals

No comments