Apc 3000T User Manual Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 33
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
990-7031D, Revision 5 5/01
16
User Configuration Items
Note: Setting these items requires optional software or hardware.
Function Factory Default User Selectable Choices Description
Automatic Self-Test Every 14 days
(336 hours)
Every 7 days (168 hours), On
Startup Only, No Self-Test
Sets the interval at which the UPS will execute a self-test.
UPS ID UPS_IDEN Up to eight characters to define
the UPS.
Use this field to uniquely identify the UPS for network
management purposes.
Date of Last Battery Replacement Manufacture Date Date of Battery Replacement Reset this date on battery replacement.
Minimum Capacity Before Return from
Shutdown
0 percent 15, 50, 90 percent The UPS will charge its batteries to the specified percentage
before return from a shutdown.
Sensitivity Normal Reduced, Low Set lower than normal sensitivity to avoid lowered battery
capacity and service life in situations where the load can
tolerate minor power disturbances.
Duration of Low Battery Warning 2 minutes 5, 7, 10 minutes Sets the time before shutdown at which the UPS issues a low
battery warning. Set higher than the default only if the OS
needs the time for graceful shutdown.
Alarm Delay After Line Fail 5 second delay 30 second delay, At Low
Battery Condition, No Alarm
To avoid alarms for minor power glitches, set the alarm delay.
Shutdown Delay 20 seconds 180, 300, 600 seconds Sets the interval between when the UPS receives a shutdown
command and when shutdown occurs.
Synchronized Turn-on Delay 0 seconds 60, 180, 300 seconds To avoid branch circuit overload, the UPS will wait the
specified time after the return of utility power before turn-on.
High Transfer Point 229 224, 234, 239 To avoid unnecessary battery usage, set the High Transfer
Point higher if the utility voltage is chronically high and the
load is known to work well under this condition.
Low Transfer Point 177 168, 172, 182 Set the Low Transfer Point lower if the utility voltage is
chronically low and the load can tolerate this condition.
How to Determine On-Battery Run Time
Note:
UPS battery life differs based on usage and environment.
APC recommends that the battery/batteries be changed once every two years.
Tower and 5U Models - 1400VA and 2200VA Models
Typical On-Battery Runtime Versus Load, in Hours
Load
(VA)
Internal
Battery
1
Battery
Pack
2
Battery
Packs
3
Battery
Packs
4
Battery
Packs
5
Battery
Packs
6
Battery
Packs
7
Battery
Packs
8
Battery
Packs
9
Battery
Packs
10
Battery
Packs
100 4.50 9.75 15.42 21.08 26.75 32.42 38.08 43.75 49.41 55.08 60.75
200 2.75 6.25 9.75 13.50 17.25 21.08 24.83 28.58 32.33 36.17 39.92
300 1.83 4.50 7.08 9.67 12.50 15.33 18.08 20.92 23.75 26.58 29.42
400 1.33 3.42 5.42 7.50 9.58 11.83 14.08 16.33 18.58 20.75 23.00
500 1.05 2.67 4.42 6.08 7.83 9.50 11.33 13.25 15.08 16.92 18.75
600 0.85 2.17 3.67 5.08 6.50 8.00 9.42 11.00 12.58 14.17 15.75
700 0.68 1.75 3.00 4.25 5.50 6.75 8.00 9.26 10.67 12.00 13.33
800 0.58 1.50 2.58 3.75 4.83 5.92 7.08 8.17 9.25 10.50 11.67
900 0.48 1.27 2.25 3.25 4.25 5.25 6.25 7.25 8.25 9.17 10.25
1000 0.43 1.12 2.00 2.83 3.75 4.67 5.58 6.42 7.33 8.25 9.17
1200 0.33 0.88 1.52 2.25 3.00 3.75 4.50 5.25 6.00 6.75 7.50
1400 0.27 0.70 1.22 1.83 2.50 3.08 3.75 4.42 5.00 5.67 6.25
1600 0.22 0.57 1.00 1.47 2.00 2.58 3.08 3.67 4.17 4.75 5.25
1800 0.18 0.48 0.87 1.25 1.75 2.17 2.67 3.17 3.67 4.17 4.67
2000 0.15 0.42 0.73 1.08 1.45 1.92 2.33 2.75 3.17 3.67 4.08
Page view 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 32 33

Comments to this Manuals

No comments