Site Preparation
InfraStruXure for Wiring Closets and Computer Rooms 7
Electrical requirements and safety
Electrical input
Electrical
Hazard
Consult your UPS and power distribution manuals for detailed electrical
requirements and installation instructions.
Consult your national and local codes for requirements other than those listed in
the manuals included with your products.
The UPS contains internal batteries and may present a shock hazard even when
disconnected from the branch circuit (mains). See the safety information in your
UPS manual.
Product
Connection
Method
Connection Type
Voltages
Supported
Symmetra RM 2–6 kVA Hard-wired 40 A, 2-pole (external); #10AWG (6 mm
2
) 230
Symmetra LX 48 kVA Hard-wired 50 A, 2-pole (external); #6AWG (16 mm²) 230
Symmetra LX 8 –16 kVA Hard-wired 100 A, 2-pole (external); #3AWG (25 mm²) 230
Smart-UPS 1500 Cord-connected IEC 320 C14 230
Smart-UPS 2200 Cord-connected IEC 320 C20, Schuko CEE 7/EU1-16P, or
British BS136A
230
Smart-UPS 3000 Cord-connected IEC 320 C20, Schuko CEE 7/EU1-16P, or
British BS136A
230
Smart-UPS 5000 Hard-wired 3-wire, #10AWG (6 mm
2
) 230
Smart-UPS RT 2000 Cord-connected IEC 320 C20, Schuko CEE 7/EU1-16P, or
British BS136A
230
Smart-UPS RT 3000 Cord-connected IEC 320 C20, Schuko CEE 7/EU1-16P, or
British BS136A
230
Smart-UPS RT 5000 Hard-wired 3-wire, #10AWG (6 mm
2
) 230
Smart-UPS RT 7500 Hard-wired 50 A, 2-pole, #8AWG (10 mm
2
), or
50 A, 4-pole, #8AWG (10 mm
2
)
230
Smart-UPS RT 10000 Hard-wired 63 A, 2-pole, #6AWG (16 mm
2
), or
63 A, 4-pole, #6AWG (16 mm
2
)
230
Cord-Connected PDU Cord-connected IEC 320 C19 230