APC Smart-UPS VT Specifications Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
4
Connect APC communication options
Note: The cable routing of the power chute software and
the temperature sensor is identical.
Note: The temperature sensor is provided in a plastic bag
attached to the front of the UPS behind the front panel.
Turn the screw below the
user interface display to the
right to the unlocked position.
Lift the front panel to free
the two tabs at the bottom of
the enclosure.
Remove the two screws
from the cable-inlet at the
front and remove the cable-
inlet plate.
Guide the cable through
the hole in the bottom plate
and up through the cable-
inlet.
Guide the cable through
the side panel hole and run
the cable upwards inside the
panel.
Pull the cable out of the
side panel through the hole
closest to the Network
Management Card area.
Plug the cable into the
probe socket / PowerChute
inlet.
Reattach the cable-inlet
plate (
).
Specifications
Warning: The UPS must be supplied from a 380/220 V,
400/230 V or 415/240 V L1, L2, L3, N, PE, 50 Hz.
AC input
AC output
Network
Management
card
10 kVA
UPS ratings 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70
Nominal input current (A)
1
13.0 12.3 11.9
Max. input current (A)
2
14.3 13.5 13.1
Input current limit (A)
3
16.8 16.8 16.8
1
Input current based on rated load and batteries fully charged.
2
Input current based on fully battery recharge, nominal voltage and rated load.
3
Current limitation through electronic current limiting is based on full battery
recharge and -15% input voltage.
15 kVA 20 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70
Nominal input current (A)
1
19.4 18.5 17.8 26.0 24.7 23.8
Max. input current (A)
2
21.4 20.3 19.6 28.6 27.2 26.2
Input current limit (A)
3
25.2 25.2 25.2 33.8 33.8 33.8
1
Input current based on rated load and batteries fully charged.
2
Input current based on fully battery recharge, nominal voltage and rated load.
3
Current limitation through electronic current limiting is based on full battery
recharge and -15% input voltage.
30 kVA 40 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70
Nominal input current (A)
1
38.6 36.7 35.3 51.7 49.1 47.3
Max. input current (A)
2
42.5 40.3 38.9 56.8 54.0 52.1
Input current limit (A)
3
50.1 50.1 50.1 66.9 66.9 66.9
1
Input current based on rated load and batteries fully charged.
2
Input current based on fully battery recharge, nominal voltage and rated load.
3
Current limitation through electronic current limiting is based on full battery
recharge and -15% input voltage.
10 kVA
UPS ratings 380 V 400 V 415 V
Nominal output current (A) 15.2 14.4 13.9
15 kVA 20 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Nominal output current (A) 22.8 21.7 20.9 30.4 28.9 27.8
30 kVA 40 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Nominal output current (A) 45.6 43.3 41.7 60.8 57.7 55.6
Page view 3
1 2 3 4 5 6

Comments to this Manuals

No comments