Battery input
Bypass input
Recommended current protection
Note: AC input/output over-current protection and AC
input/output disconnect must be provided by the customer
Recommended cable sizes
Note: The recommended cable sizes are based on an
environment with an ambient temperature of 30°C.
Note: Use Molex lug type or equivalent, and crimp to
manufacturer’s specifications.
Warning: At 100% switch mode load, the neutral must
be rated for 200% phase current.
Minimum breaker settings
Recommended lug size and torque value
Note: Power terminal lug diameter: 6 mm. Torque value: 7
Nm.
UPS ratings
15 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Nominal voltage (V) ± 192 ± 192 ± 192 ± 192 ± 192
External battery fuse (A) 125 125 125 125 125
125 1.6-1.75 V/cell (automatic, depending on load)
10 kVA
UPS ratings 380 V 400 V 415 V
Input frequency (Hz) 50-60 50-60 50-60
Nominal input current (A)
1
13.0 12.3 11.9
1
Input current based on rated load and batteries fully charged.
15 kVA 20 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Input frequency (Hz) 50-60 50-60 50-60 50-60 50-60 50-60
Nominal input current (A)
1
19.4 18.5 17.8 26.0 24.7 23.8
1
Input current based on rated load and batteries fully charged.
30 kVA 40 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Nominal voltage (V) 50-60 50-60 50-60 50-60 50-60 50-60
Nominal input current (A)
1
38.6 36.7 35.3 51.7 49.1 47.3
1
Input current based on rated load and batteries fully charged.
Q1
1
Q5
2
Q3 Q2
10 kVA
16 16 16 16
15 kVA
25 25 25 25
20 kVA
35 35 35 35
30 kVA
50 50 50 50
40 kVA
63 63 63 63
1
Required upstream current protection, mains input: gL type fuse.
2
Required upstream current protection, bypass input: gL type fuse.
Mains input
[mm
2
]
AC output
[mm
2
]
Battery input
[mm
2
] 70ºC
Wire
Bypass input
[mm
2
]
10 kVA
2.5 2.5 6 2.5
15 kVA
66106
20 kVA
10 10 16 10
30 kVA
16 16 35 16
40 kVA
25 25 50 25
Internal
fault
1
800%
overload
bypass
operation
150%
overload
normal/
battery
operation
125%
overload
normal/
battery
operation
Conti-
nuously
10 kVA
Mains input 2 kA 16.4 A
Bypass input 1.7 kA 121.5 A 16.7 A
Output 9 kA 121.5 A 22.8 A 19 A 16.7 A
Duration <10 ms 500 ms 10 s 10 min.
15 kVA
Mains input 2.1 kA 24.6 A
Bypass input 1.8 kA 182 A 25.1 A
Output 9 kA 182 A 34.2 A 25.4 A 25.1 A
Duration <10 ms 500 ms 60 s 10 min.
20 kVA
Mains input 2.5 kA 32.5 A
Bypass input 2.3 kA 244 A 33.4 A
Output 9 kA 244 A 68.4 A 57 A 33.4 A
Duration <10 ms 500 ms 60 s 10 min.
30 kVA
Mains input 2.5 kA 32.5 A
Bypass input 2.3 kA 244 A 33.4 A
Output 9 kA 244 A 68.4 A 57 A 33.4 A
Duration <10 ms 500 ms 60 s 10 min.
40 kVA
Mains input 3 kA 65.6 A
Bypass input 2.3 kA 487 A 66.9 A
Output 14 kA 487 A 91.2 A 76 A 66.9 A
Duration <10 ms 500 ms 60 s 10 min.
1
For the output value, the short-circuit level is indicated.