Smart-UPS X 2000/2200/3000 Vac XL 120/208/230/240 VA Tower/Rack-Mount 4U 10
General settings
Configure these settings at any time, using the display interface, PowerChute
software, or a network management
card.
Function Factory Default Options Description
High Transfer
Point
Low Voltage To avoid unnecessary battery usage, set the transfer
point higher if the utility voltage is chronically high
and the connected equipment is known to work under
this condition. The
POWER QUALITY setting will
automatically change this setting.
Note: Use the Advanced Menus to configure this
setting.
100 V: 108 Vac 108-114 Vac
110 V: 116 Vac 116-125 Vac
120 V: 127 Vac 127-136 Vac
127 V: 134 Vac 134-143 Vac
High Voltage
200 V: 216 Vac 216-228 Vac
208 V: 220 Vac 220-235 Vac
220 V: 242 Vac 242-254 Vac
230 V: 253 Vac 253-265 Vac
240 V: 264 Vac 264-276 Vac
Low Transfer
Point
Low Voltage Set the transfer point lower if the utility voltage is
chronically low and the connected equipment can
tolerate this condition.The
POWER QUALITY setting
will automatically change this setting.
Note: Use the Advanced Menus to configure this
setting.
100 V: 92 Vac 86-92 Vac
110 V: 98 Vac 89-98 Vac
120 V: 106 Vac 97-106 Vac
127 V: 112 Vac 103-112 Vac
High Voltage
200 V: 184 Vac 172-184 Vac
208 V: 184 Vac 169-184 Vac
220 V: 198 Vac 186-198 Vac
230 V: 207 Vac 195-207 Vac
240 V: 216 Vac 204-216 Vac
Green Mode If the UPS input voltage is between the high transfer point and the lower transfer point, the UPS will
operate in Green Mode. Configure this setting using the Advanced menus.
Transfer
Sensitivity
Normal • Normal
•Reduced
•Low
Select the level of sensitivity to power events that the
UPS will tolerate.
• Normal: The UPS will go on battery power more
often to provide the cleanest power supply to the
connected equipment.
• Reduced: The UPS will tolerate some fluctuations
in power.
• Low: The UPS will tolerate more fluctuations in
power and will go on battery power less often.
If the connected load is sensitive to power
disturbances, set the sensitivity to Normal using the
advanced Configuration menu.