Smart-UPS X 2000/2200/3000 Vac XL 120/208/230/240 VA Tower/Rack-Mount 4U
11
Low Runtime
Warning
150 sec Value set in seconds The UPS will emit an audible alarm when the
remaining runtime has reached this level.
Date of Last
Battery
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On On/Off The UPS will mute all audible alarms if this is set to
Off or when any of the display buttons are pressed.
Display
Dimmer
Always on • Always on
• Auto dim
• Auto off
To conserve energy, the display panel illumination
dims or extinguishes when no events are present. Full
display panel illumination returns when the UPS
changes status as a result of an event or if the display
panel is touched.
Auto Self-Test
Interval Setting
On start up and every
14 days there after
• Last test + 14 days
• Last test + 7 days
• Turn on + 14 days
• Turn on + 7 days
• On startup only
•Never
The interval at which the UPS will execute a self-test.
The batteries much be charged to at least 70%
capacity to perform the self-test.
Reset to
Factory Default
No Yes/No Restore the UPS factory default settings.
Function Factory Default Options Description