R Turn dumb BYE Only on 3rd gen SmartUPS, SmartUPS v/s,
BackUPS Pro. Must send enter smart mode
command to resume comms.
S Soft
shutdown
OK Command executes after grace period. UPS goes
online when power returns. Only works when on
battery.
U Simulate
power failure
!, then $ See Alert messages section for info on ! and $.
V Old firmware
revision
"GWD" or "IWI" See Interpretation of the Old Firmware Revision
W Self test OK Tests battery, like pushing button on the front
panel. Results stored in "X"
X Self test
results
OK Possible values:
• OK = good battery
• BT = failed due to insufficient capacity
• NG = failed due to overload
NO = no results available (no test performed
in last 5 minutes)
Y Enter smart
mode
SM This must be sent before any other commands will
work. See also turn dumb command to exit smart
mode.
Z Shutdown
immediately
n/a Send twice with > 1.5s delay between chars. UPS
switches load off immediately (no grace period)
a Protocol info long string Returns three main sections delimited by periods:
• Protocol version
• Alert messages (aka async notifiers)
• Valid commands
b Firmware
revision
50.9.D See Interpretation of the New Firmware Revision.
Decoding the example:
• 50 = SKU (variable length)
• 9 = firmware revision
D = country code (D=USA, I=International,
A=Asia, J=Japan, M=Canada)
c UPS local id UPS_IDEN Writable variable. Up to 8 letter identifier for
keeping track of your hardware.
e Return
threshold
00 Writable variable. Minimum battery charge %
before UPS will return online after a soft shutdown.
Possible values:
• 00 = 00% (UPS turns on immediately)
• 01 = 15%
• 02 = 25%
• 03 = 90%