f Battery level
%
099.0 Percentage of battery charge remaining
g Nominal
battery
voltage
024 The battery voltage that's expected to be present
in the UPS normally. This is a constant based on
the type, number, and wiring of batteries in the
UPS. Typically "012", "024" or "048".
h Measure-UPS
ambient
humidity (%)
042.4 Percentage. Only works on models with
Measure-UPS SmartSlot card.
i Measure-UPS
dry contacts
00 Bitmapped hex variable. Mapping:
• 10 = contact 1
• 20 = contact 2
• 40 = contact 3
• 80 = contact 4
j Estimated
runtime
0327: Value is in minutes. Terminated with a colon.
k Alarm delay 0 Writable variable. Controls behavior of UPS
beeper. Possible values:
• 0 = 5 second delay after power fail
• T = 30 second delay
• L = alarm at low battery only
• N = no alarm
l Low transfer
voltage
103 Writable variable. UPS goes on battery when
voltage drops below this point.
m Manufacture
date
11/29/96 Format may vary by country (MM/DD/YY vs
DD/MM/YY). Unique within groups of UPSes
(production runs)
n Serial number WS9643050926 Unique for each UPS
o Nominal
Output
Voltage
115 Expected output voltage when running on
batteries. May be a writable variable on
220/230/240 VAC units.
p Shutdown
grace delay
020 Seconds. Writable variable. Sets the delay before
soft shutdown completes. (020/180/300/600)
q Low battery
warning
02 Minutes. Writable variable. The UPS will report a
low battery condition this many minutes before it
runs out of power
r Wakeup
delay
000 Seconds. Writable variable. The UPS will wait this
many seconds after reaching the minimum charge
before returning online. (000/060/180/300)
s Sensitivity H Writable variable. Possible values:
• H = highest
• M = medium
• L = lowest
• A = autoadjust (Matrix only)