13InRow Fluid Cooled RD Installation
Connections Overview
All connections to and from the equipment can be made through either the top or the bottom of the
equipment. Once the connectors are sweated or soldered into place, the equipment can be connected and
disconnected without soldering, welding, or gluing. See the following tables for information about the
sizes and types of connectors.
Warning: Make electrical connections in accordance with all local and national codes.
Power connections
Piping connections
Insulation
Apply provided insulation to water lines to protect personnel and to minimize condensation.
Note: Using either tape or glue, completely seal the insulation boots covering the unused
supply and return connections.
Model Voltage
Frequency
(Hz) MCA MOP FLA
LRA
(Compressor)
ACRD200
208-240 60 25 40 N/A 87.5
ACRD201
220-240 50 N/A N/A 28 N/A
Above data is based on maximum operating conditions.
Consult local and national codes for wire size, conduit requirements and overload protection.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
FLA - Full Load Amps
LRA - Locked Rotor Amps
Connection Type ACRD100/101
Fluid input
Brazed* 7/8-in OD (nominal) copper
Fluid return
Brazed* 7/8-in OD (nominal) copper
Condensate drain
3/16-in ID
5/16-in OD
* Use the provided gaskets to prevent leakage.