990-2283 Smart-UPS® VT 10-40kVA 400V Site Preparation and Installation Manual 13
Site Preparation
Installation Space Requirements
Clearance
*) All physical installations must comply with local standards.
Note
Allow for enough working space behind the Enclosure for electrical work to be carried
out (e.g. if you want to connect other equipment at a later stage).
Space requirements 523mm Enclosure 352mm Enclosure
Minimum clearance above Enclosure (A) 500 500
Enclosure depth (B) 906 906
Enclosure width (C) 523 352
Minimum free rear space for airflow* (D) 100 100
Minimum front clearance (E) 1000 1000
No side clearance required (add width of Enclosure
Stabilizing Brackets (2x80mm) for floor anchoring
protection if applicable)*
00
Total installation depth, inclusive of Front Panel, and
minimum front and rear clearances (G)
2006 2006
(E)
(D)
(A)
(B)
(G)
(C)
(C)
(A)
(D)
(B)
(G)
(E)