Site Preparation – Operating Environment
990-2283 Smart-UPS® VT 10-40kVA 400V Site Preparation and Installation Manual 17
Recommended current protection
Note 1:
If the available fault current of the installation is below 30kA, a lower Icu-rated breaker can be used.
Note 2:
For breaker settings, refer to below tables listing available overload currents.
Note 3:
Maximum rating of a single fuse configuration if the internal bypass must be protected during a load
short circuit. Selectivity is not ensured by the configuration.
Note 4:
Maximum DC currents in Smart-UPS VT. Size cable for maximum DC currents as in table above.
Use 150° cable for installation.
Note
AC output over-current protection and AC output disconnect must be provided by the
customer.
Dual/single
mains
configuration
Connection 10kVA 15kVA 20kVA 30kVA 40kVA Notes
Dual Mains input 20A
breaker
(30kA)
35A
breaker
(30kA)
50A
breaker
(30kA)
63A
breaker
(30kA)
80A
breaker
(30kA)
1+2
Dual Bypass input 20A
breaker
(30kAIC)
35A
breaker
(30kA)
50A
breaker
(30kA)
63A
breaker
(30kA)
80A
breaker
(30kA)
1+2
Single Mains/Bypass
input
20A
breaker
(30kA)
35A
breaker
(30kA)
50A
breaker
(30kA)
63A
breaker
(30kA)
80A
breaker
(30kA)
1+2
Any Output 20A
Class
gL (gG)
fuse
35A
Class
gL (gG)
fuse
50A
Class
gL (gG)
fuse
63A
Class
gL (gG)
fuse
80A
Class gL
(gG) fuse
3
DC Max. batt.
Voltage ±192V
22A 33A 44A 66A 88A 4
DC Low. batt.
Voltage ±154V
27.5A 41.2A 55A 82.5A 109.9A 4