APC Smart-UPS VT Installation Manual Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
990-2283 Smart-UPS® VT 10-40kVA 400V Site Preparation and Installation Manual 37
Communication Wiring to EPO and
Optional Equipment
Pin connections J106 and J108 (EPO)
Note
EPO switch and wiring must be suited for use in a SELV circuit.
N
N
N
L
1
L
1
L
1
L
2
L
2
L
2
L
3
L
3
L
3
J106 Pin Connections:
8 Ext. charging control return
7 External control of charging
6 Q3 active return
5 Q3 active
4 Battery measurement supply*
3 Battery unit quantity*
2 Max. battery temperature*
1 Battery measurement return*
* Can be used with External Battery
Temperature Sensor, and APC
Battery Breaker Box.
J108 Pin Connections:
1 Normally open EPO
2 Normally open EPO return
3 Normally closed EPO
4 Normally closed EPO return
5 +24V SELV supply
6 SELV ground
Page view 44