Operation: Total Power Off
28 Automatic Transfer Switch with Power Distribution
3. Set the Source 2 switch on the ATS to OFF (
):
a. Set the selector switch on the Source 2 switch to Manual.
The operating lever will swing out when the selector switch is in Manual.
b. Turn the Source 2 switch counterclockwise to OFF (
). You can use the operating lever key
(provided), for easier operation.
4. Set the main Source 1 circuit breaker to OFF (
).
5. Set the main Source 2 circuit breaker to OFF (
). If Source 2 is a generator, set the generator
control switch to OFF (
), or set the generator control switch to Manual, if OFF is not an
option.