APC Automatic Disconnect Switch Specifications Page 53

  • Download
  • Add to my manuals
  • Print
  • Page
    / 102
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 52
Automatic Transfer Switch with Power Distribution 43
Alarms
View Active Alarms
View a list of all alarms that exist presently. When an alarm is present, the ATS display interface Alarm LED is
red. Choosing this option to View Active Alarms turns the LED off.
Alarm/Event Log
Alarm Setup
View Active Alarms
Alarm/Event Log
Alarm Setup
Alarm Beeper
The following items are available on this menu:
New Logged Items View only alarms and events logged since New Logged Items was last viewed.
When a new alarm is present, the ATS display interface Check Log LED is orange.
Choosing this option, New Logged Items, turns the LED off.
Entire Log View every item in the alarm/event log. When a new alarm is added to the log, the
ATS display interface Check Log LED is orange. Choosing this option, Entire
Log, turns the LED off.
Clear Log Erase all of the items currently in the alarm/event log.
Clr Latched Alarms Erase the latched alarms currently in the alarm/event log. See “Clearing latched
alarms” on page 44 for more information.
Configure the alarm limits (or thresholds) on this menu:
Loading Limits Iout-Alarm Limits:
Low: If the output current of any phase falls below this value, an alarm condition
exists. The value is set as a percentage of the ATS rating, and also shown in amps.
High: If the output current of any phase exceeds this value, an alarm condition
exists. The value is set as a percentage of the ATS rating, and also shown in amps.
Neut: If the output neutral current exceeds this value, an alarm condition exists.
The value is set as a percentage of the ATS rating, and also shown in amps.
Voltage Limits Vout-Alarm Limits:
Low: If the output voltage of any phase falls below this value, an alarm condition
exists. The value is set as a percentage of the nominal system voltage, and also
shown in volts.
High: If the output voltage of any phase exceeds this value, an alarm condition
exists. The value is set as a percentage of the nominal system voltage, and also
shown in volts.
Page view 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 101 102

Comments to this Manuals

No comments