UPS Overview – Operation Modes
990-2819 Smart-UPS® VT ISX 20-30 kVA, 208/220/480V Operation 15
Turn into mechanical bypass using the Mechanical Bypass Lever
From the Main Menu, select Control and press ENTER.
Use UP/DOWN key to navigate to UPS into Bypass and press ENTER.
Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER.
Remove UPS Front Panel.
Turn the Mechanical Bypass Lever upwards to activate the internal mechanical bypass switch.
The load will now be supported directly by utility power.
Caution
The load is not protected by the UPS when the internal mechanical bypass system is
active, and, the power is not conditioned.
Note
If the UPS is running and controllable through the display, carry out steps 1 through 6.
If not, go directly to step 4.