Metered-by-Outlet With Switching Rack PDU User Guide44
olRbootTime
Access: Administrator, Device User, and Outlet User, but only for outlets to which the user is assigned.
Description: Set or view the amount of time an outlet will remain off for a Reboot Delayed command
(see “olDlyReboot” on page 38).
Example 1: To view the time set for outlets 3 and 5 through 7 to remain off during a reboot, type:
apc> olRbootTime 3,5-7
E000: Success
3: BobbysServer: 4 sec
5: BillysServer: 5 sec
6: JoesServer: 7 sec
7: JacksServer: 2 sec
Example 2: To set the time for outlets 3 and 5 through 7 to remain off during a reboot, type:
apc> olRbootTime 3,5-7 10
E000: Success
3: BobbysServer: 10 sec
5: BillysServer: 10 sec
6: JoesServer: 10 sec
7: JacksServer: 10 sec
olReading
Access: Administrator, Device User, and Outlet User, but only for outlets to which the user is assigned.
Description: Displays a reading/measurement from an outlet or a group of outlets.
olReading [id#:] <all | outlet name | outlet#> <current | power | energy>
Example 1: To view the current readings of outlets 1 through 3, type:
apc> olReading 1-3 current
E000: Success
1: Outlet 1: 5.1 A
2: Outlet 2: 1.9 A
3: BobbysServer: 2.3 A
Example 2: To view the power readings of outlets 1 through 4 on guest Rack PDU 2, type:
apc> olReading 2:1-3 power
E000: Success
1: Outlet 1: 0 W
2: Outlet 2: 0 W
3: BobbysServer: 0 W